Reference Laboratory :
LABORATORY SERVICES CENTER of RAMA INDUSTRIAL GROUP consists of laboratories located in cities Urmia (RAMA ELECTRIC LABORATORY) and Eshtehard (RAMA PARSIAN LABORATORY) was established in 2005, considering targets as below priorities :
1- Doing tests which are required to RAMA INDUSTRIAL GROUP.
2- Performing laboratory services for Iran Standard and Industrial Researches Organization and other costumers, considering the demands through Iran and in order to utilize the facilities optimally.
RAMA INDUSTRIAL GROUP consists of RAMA ELECTRIC Co. and RAMA PARSIAN Co. (former ATRO ELECTRIC Co.) companies located in Urmia and Eshtehard cities, produces various types of enameled and annealed aluminum and copper wires with round and rectangular sections and ballasts and transes for luminaries. Since RAMA INDUSTRIAL GROUP has special approach, in terms of quality and establishment of management system for doing activities and most of its products has got main national and international standards, therefore, the management decided to establish the laboratory services center according to requirements of ISO/IEC 17025.
In 2008, ATRO ELECTRIC Co., renamed to RAMA PARSIAN Co. and the requirements of ISO-IEC 17025 was established in the laboratory services center. At present, the laboratory services center is certified by NATIONAL ACCREDITATION CENTER of IRAN (NACI) based on ISO-IEC 17025.
The services which are performed by the laboratory services center, consists of: Doing Tests of Annealed wires and enameled round and rectangular wires for all existing diameters and general, safety and performance requirements for ballasts and also transformers for all existing powers of halogen lamps according to national (ISIRI) and international (IEC) standards or any other requested standard considering requirements of the laboratory services center and also offering special interpretations and expertize on test results and specifications of the samples.
Laboratory activities in Urmia and Eshtehard perform as bellow specifications and ranges:
-
Dimensional, mechanical, electrical, thermal and chemical tests for enameled round and rectangular copper wire and enameled round aluminum wire in various thermal classes according to related factory, national or international standards.
-
General and safety tests and also performance tests on inductive ballasts for different types of discharge lamps with low or high pressure gas lamps such as: compact, fluorescent, mercury vapor, sodium vapor and metal halide and also transformers for tungsten-halogen lamps according to related factory, national or international standards. Moreover, identifying the Label of Energy for inductive fluorescent ballasts.
Address of RAMA PARSIAN Co. ballast and enameled wire test laboratories:
2ndGolchehr Ave. West Dr. Hessabi Blvd, Abourayhan Blvd, Eshtehard industrial zone, Karaj, Iran.
Tel : +98 26 3777 3091~3 Fax: +98 26 3777 3792
General requirements and methods of test for winding wires :
According to standards:
|
Name of Test:
|
row
|
ISIRI:6998, 6892
IEC:60317, 60851
|
Dimensions, elongation, springiness, flexibility and adherence, resistance to abrasion, electrical resistance, enamelcontinuity, heat shock, cut through, breakdown voltage, resistance to solvents, tangent delta, solderability, packaging
|
1
|
ISIRI:6998, 6892, 2679
IEC:60317, 60851, 60172
|
thermal Index
|
2
|
Ballast laboratory as bellow scope:
General and safety tests consist of:
According to standards:
|
Name of Test:
|
row
|
ISIRI:7644-1, 7644-2-8, 7644-2-9,
700-1, 3824
IEC:61347-1, 61347-2-8, 61347-2-9
|
Marking, Protection against accidental contact with live parts, Terminals, Provisions for earthing, Moisture resistance and insulation, Electric strength, Thermal endurance, test for windings Screws, current-carrying parts and connections, Resistance to heat and fire (ball pressure,
glow-wire, needle-flame), Resistance to tracking, Resistance to corrosion, High voltage impulse testing
|
1
|
ISIRI: 7644-2-8, 7644-2-9,
700-1, 3824
IEC: 61347-2-8, 61347-2-9
|
Ballast heating
|
2
|
ISIRI:7644-1, 7644-2-9,
700-1, 3824
IEC:61347-1, 61347-2-9
|
Creepage distances and clearances
|
3
|
ISIRI:7644-1, 7644-2-9,
7644-2-8
IEC:61347-1, 61347-2-8, 61347-2-9
|
Construction
|
4
|
Performance tests consist of:
According to standards:
|
Name of Test:
|
row
|
ISIRI:700-2 ,5190
IEC: 60921, 60923
|
Marking, Current waveform, Supply current, Magnetic screening, Circuit power-factor
|
1
|
ISIRI:700-2
IEC: 60921
|
open-circuit voltage for lamp or starter, Maximum current in any lead to a cathode, Pre-heating conditions, Lamp power and current
|
2
|
ISIRI:5190
IEC:60923
|
open-circuit voltage(minimum voltage for stable operation),Ballasts designed to operate at various supply voltage, Short circuit current and run-up conditions, Ballast setting
|
3
|
Energy labeling test:
According to standards:
|
Name of Test:
|
row
|
ISIRI:10759
|
identifying the Label of Energy for inductive fluorescent ballasts
|
1
|
Address : RAMA ELECTRIC Co. ballast test laboratory,
Next to Passport Office, Basij Blvd., Khatam-al-anbia Blvd., Urmia, Iran.
Tel: +98 44 3278 0009 & +98 44 3277 5236
Fax: +98 44 3277 3380
Ballast laboratory as bellow scope:
General and safety tests consist of:
According to standards:
|
Name of Test:
|
row
|
ISIRI:7644-1, 7644-2-8, 7644-2-9,
700-1, 3824
IEC:61347-1, 61347-2-8, 61347-2-9
|
Marking, Protection against accidental contact with live parts, Terminals, Provisions for earthing, Moisture resistance and insulation, Electric strength, Thermal endurance, test for windings Screws, current-carrying parts and connections, Resistance to heat and fire (ball pressure,
glow-wire, needle-flame), Resistance to tracking, Resistance to corrosion, High voltage impulse testing
|
1
|
ISIRI: 7644-2-8, 7644-2-9,
700-1, 3824
IEC: 61347-2-8, 61347-2-9
|
Ballast heating
|
2
|
ISIRI:7644-1, 7644-2-9,
700-1, 3824
IEC:61347-1, 61347-2-9
|
Creepage distances and clearances
|
3
|
ISIRI:7644-1, 7644-2-9,
7644-2-8
IEC:61347-1, 61347-2-8, 61347-2-9
|
Construction
|
4
|
Performance tests consist of:
According to standards:
|
Name of Test:
|
row
|
ISIRI:700-2 ,5190
IEC: 60921, 60923
|
Marking, Current waveform, Supply current, Magnetic screening, Circuit power-factor
|
1
|
ISIRI:700-2
IEC: 60921
|
open-circuit voltage for lamp or starter, Maximum current in any lead to a cathode, Pre-heating conditions, Lamp power and current
|
2
|
ISIRI:5190
IEC:60923
|
open-circuit voltage(minimum voltage for stable operation),Ballasts designed to operate at various supply voltage, Short circuit current and run-up conditions, Ballast setting
|
3
|
Energy labeling test:
According to standards:
|
Name of Test:
|
row
|
ISIRI:10759
|
identifying the Label of Energy for inductive and electronic fluorescent ballasts
|
1
|
Testing transformers for tungsten-halogen lamps consists of:
According to standards:
|
Name of Test:
|
row
|
ISIRI:6920-1,6920-2-6
|
Marking and other information, Protection against access to dangerous current-carrying parts,
Changing output voltage adjustment, Loaded output voltage and current, Load-free output voltage, Short-circuit voltage,
Heating, Protection againstshort-circuit&overload, Mechanical strength, Protection againstdust,
Solid things andharmful moisture,
Insulation resistance&dielectric strength, Construction, Terminals,
Creepage and insulating distances and clearances, Resistance to heat, abnormal heat, fire&tracking,
Resistance tocorrosion
|
1
|
Electronic Ballasts:
General and safety tests consist of:
According to standards:
|
Name of Test:
|
row
|
ISIRI:6196
IEC:60928
|
Marking, Protection against electric shock, Electric strength, Resistance to corrosion,
|
1
|
ISIRI:6196,5920-1
IEC:60928
|
Terminals, Provision for earthling ,Screws, current carrying parts and connections
|
2
|
ISIRI:6196,3626
IEC:60928
|
Creepage distance and clearances
|
3
|
ISIRI:6196,2868
IEC:60928,60990
|
Protection against accidental contact with live parts
|
4
|
ISIRI:6196
IEC:60928,60479
|
Moisture resistance and insulation
|
5
|
ISIRI:6196,687
IEC:60928
|
Abnormal conditions
|
6
|
ISIRI:6196,5920-1,3653
IEC:60928,60990
ISO:4046
|
Fault conditions
|
7
|
ISIRI:6196,5920-1, 3653,3424,3685
IEC:60928
ISO:4046
|
Resistance to heat and fire
|
8
|
Electronic ballasts for fluorescent lamps:
Performance tests consist of:
According to standards:
|
Name of Test:
|
row
|
ISIRI:6195
IEC:60929
|
Marking, Operating conditions, Circuit power factor, Supply current, Maximum current in any lead to a cathode, Magnetic screening,
Impedance at audio frequencies, Mains transient over voltages, Operational tests for abnormal conditions, Endurance
|
1
|
ISIRI:6195,687,5211
IEC:60929
|
General statement, Starting conditions
|
2
|
ISIRI:6195
IEC:60929,610003-2
|
Current waveform
|
3
|
General and safety tests consist of:
According to standards:
|
Name of Test:
|
row
|
ISIRI:7644-2-1,7644-1
IEC:61347-2-1
ISO:3864
|
Marking
|
1
|
ISIRI:7644-2-1,7644-1
IEC:61347-2-1
|
Protection against accidental contacts
with live parts, Terminals, Provision for earthling, Moisture resistance and insulation, Electric strength, Construction
Creepage distance and clearances,
Screws & current carrying parts and connections, Resistance to heat & fire and tracking, Resistance to corrosion,
Pulse voltage of ignitors
|
2
|
ISIRI:7644-2-1,7644-1,687,5211
IEC:61347-2-1
|
Fault conditions
|
3
|
ISIRI:7644-2-1,7644-1,5920-1
687,5211
IEC:61347-2-1
|
Heating of independent starting devices
|
4
|
ISIRI:7644-2-1,1560
IEC:61347-2-1,60068-2-75
|
Mechanical strength
|
5
|
Performance tests consist of:
According to standards:
|
Name of Test:
|
row
|
ISIRI:3782
IEC:60927
|
Marking, Starting test, Non reoperating level, Endurance test
|
1
|